Details

Reactor Type Gas-Cooled Reactor (or GCR)
Model MAGNOX
Owner Nuclear Decommissioning Authority
Operator Magnox, Ltd

Timeline

Construction Start Tuesday, 1 May 1962
First Criticality Friday, 1 December 1967
First Grid Connection Saturday, 6 April 1968
Commercial Operation Monday, 30 September 1968
Permanent Shutdown Thursday, 30 June 2011

Specifications

Capacity Net 217 MWe
Capacity Gross 230 MWe
Thermal Capacity 660 MWt
Design Net Capacity 300 MWe

Operational History

Electricity Supplied (GWh)

Energy Availability Factor (%)

Total Electricity Supplied (GWh)

Reactor History

Year Reference Unit Power (MWe) Annual Time Online (Hours) Electricity Supplied (GWh) Operation Factor (%) Energy Availability Annual (%) Energy Availability Cumulative (%) Load Factor Annual (%) Load Factor Cumulative (%)
1968 - - - - - - - -
1969 - - - - - - - -
1970 212 0 1273.00 0.00 100.00 - 68.60 -
1971 212 8759 1560.45 99.40 86.90 93.40 83.60 76.10
1972 210 8736 1436.45 100.00 76.00 87.70 78.30 76.80
1973 200 8704 1265.20 99.60 63.30 81.80 72.40 75.80
1974 200 8731 1355.00 99.90 74.90 80.50 77.60 76.10
1975 204 8693 1436.50 99.50 78.90 80.20 80.60 76.80
1976 208 8714 1508.50 97.90 80.20 80.20 81.40 77.50
1977 208 8736 1555.00 100.00 85.50 80.90 85.60 78.50
1978 208 8736 1533.50 100.00 84.50 81.30 84.40 79.20
1979 208 8736 1592.00 100.00 88.00 82.00 87.60 80.00
1980 208 8736 1648.00 100.00 86.20 82.40 90.70 81.00
1981 208 8904 1688.00 100.00 85.50 82.60 91.10 81.90
1982 208 8736 1717.00 100.00 86.00 82.90 94.50 82.80
1983 217 8566 1506.50 98.00 77.40 82.50 79.50 82.60
1984 217 8736 1520.50 100.00 77.70 82.20 80.20 82.40
1985 217 8701 1661.05 99.60 83.20 82.20 87.60 82.80
1986 217 8650 1654.28 99.00 85.00 82.40 87.30 83.00
1987 217 8904 1611.46 100.00 82.90 82.40 83.40 83.00
1988 217 8530 1687.60 97.60 86.00 82.60 89.00 83.40
1989 217 8644 1457.59 99.00 82.00 82.60 76.90 83.00
1990 217 8713 1457.53 99.70 76.10 82.30 76.90 82.70
1991 217 8736 1592.09 100.00 84.30 82.40 84.00 82.80
1992 217 8857 1706.07 99.50 88.60 82.60 88.30 83.00
1993 217 8736 1770.63 100.00 92.50 83.10 93.40 83.50
1994 217 8318 1743.40 95.20 91.60 83.40 92.00 83.80
1995 217 8613 1841.31 98.30 96.70 83.90 96.90 84.30
1996 217 8641 1790.89 98.40 94.00 84.30 94.00 84.70
1997 217 8618 1832.39 98.40 96.40 84.80 96.40 85.10
1998 217 8760 1883.09 100.00 98.80 85.20 99.10 85.60
1999 217 7036 1515.45 80.30 79.30 85.00 79.70 85.40
2000 217 8685 1951.59 98.90 98.60 85.50 102.40 86.00
2001 217 8715 1939.82 99.50 98.80 85.90 102.00 86.50
2002 217 7724 1705.69 88.20 87.80 86.00 89.70 86.60
2003 217 8187 1859.37 93.50 93.40 86.20 97.80 86.90
2004 217 8187 1686.38 93.20 88.50 86.30 88.50 87.00
2005 217 3743 776.53 42.70 40.80 85.00 40.80 85.70
2006 217 0 0.00 0.00 0.00 82.60 0.00 83.30
2007 217 3178 618.00 36.30 32.50 81.30 32.50 82.00
2008 217 8241 1660.09 93.80 87.20 81.50 87.10 82.10
2009 217 6439 1265.09 73.50 66.60 81.10 66.60 81.70
2010 217 6579 1371.88 75.10 72.20 80.90 72.20 81.50
2011 217 3113 624.93 71.70 66.30 80.70 66.30 81.30

Source: Operating details - IAEA PRIS


See Also

Nuclear Power in United Kingdom

Related News

WNN articles on United Kingdom
Subscribe to receive updates on news